Abstract

West coast buildings typically use lightweight structural designs, even for Class A office building. This means the best floors use lightweight concrete on fluted decks with beam and column spacings of 30 to 35 ft. with open web joists at 10 ft. on center. Class B office building may use columns at 28 and 35 ft. with only two‐layers of plywood on wood open web joists at 24 in. on center. The resulting floor/ceiling assemblies are structurally sound but dynamically very live. Some structural damping would be expected from the introduction of partitions, but with the use of large open areas and partial height partitions, damping is limited. These assemblies have relatively low resonance frequencies and are very susceptible to any sinusoidal input force such as people walking or operation of mechanical equipment. Vibration measurements, made on four buildings after complaints were received, show the source of some of these problems. The results are compared with predictions by Murray et al. and Ungar et al. ...

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.