Abstract
Experiments on air/water two-phase flow performance were carried out using a centrifugal pump with five kinds of closed impellers, each of which has a different outlet or inlet blade angle. Results are described as follows. (1) A sudden head drop due to gas accumulation in the impeller occurs at a low inlet void fraction with high inlet or outlet blade angle of impellers. (2) A degraded pump head at a high inlet void fraction becomes higher with increasing outlet blade angle. These results are discussed in terms of numerical calculations of one-dimensional two-phase flow.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: TRANSACTIONS OF THE JAPAN SOCIETY OF MECHANICAL ENGINEERS Series B
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.