Abstract

The authors have investigated insulation diagnostic technique for gas-insulated switchgear (GIS) by detecting partial discharge (PD) signals, particularly PD current, PD-induced electromagnetic wave and AE signal. So far, we have experimentally shown that discharge type such as streamer and leader-type discharge can be discriminated by introducing an amplitude ratio of the positive peak value to the negative one of the first-incoming electromagnetic wave with UHF method in the 66kV model GIS. In this paper, we investigate the influence of GIS tank size on propagation properties of PD-induced electromagnetic wave by finite difference time domain (FD-TD) method to derive a criterion to discriminate discharge type. From the calculated results, we discuss the influences of GIS tank size and sensor position on discrimination of discharge type in terms of risk assessment of GIS with focusing on the influence of higher TE modes, especially TE11 mode, of propagating electromagnetic wave.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.