Material balance calculation was adopted to a wet flue gas desulfurization (WFGD) system for exploring impacts of gas-gas heater (GGH). Effects of GGH on flue and water consumption were analyzed. Results showed that inlet flue temperature of desulfurization tower reduced by 3.4 °C at 100% load after installation of GGH. Exhausted gas temperature of system increased by 34.9°C. The heat release of original flue in desulfurization tower reduced by 43.72%. Plume rise height was significantly improved. Water evaporation in desulfurization tower declined by 42.07%.Amount of addendum water reduced by 39.06%, and water vapor carried by flue decreased by 19.78% at the outlet of WFGD. Therefore, operation condition of flue emission is improved and water consumption decreases with GGH.