Abstract

At present, in the background of the multiphase rectifier system is widely used in medium voltage ship power system, the influence of DC grounding mode on the characteristics of DC monopole fault is analyzed for series 12-pulse uncontrolled rectifier system and paralleled 12-pulse uncontrolled rectifier system respectively. By establishing the electromagnetic transient model of the medium voltage power system under different topologies, fault voltage, recovery speed and fault current under different grounding modes are simulated and studied, and the fault mechanism is deeply analyzed, and the advantages and disadvantages of different grounding modes are compared. As a conclusion, for series 12-pulse rectifier system, the way of high impedance grounding through the middle point of the two series rectifier bridges is proposed. For paralleled 12-pulse rectifier system, high resistance grounding mode through the middle point of split capacitances on dc side is proposed, they are beneficial to improve the stability and transient performance of the system. That it is beneficial to improve the stability and transient performance of the system.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.