Abstract

This paper is focused on the electrical and mechanical performance of aluminum-copper hybrid busbars subjected to corrosion over time. Two different types of hybrid busbars with joints produced by conventional fastening with M8 hexagonal socket head bolt-nut pairs made from medium carbon steel and by a new injection lap riveting process with semi-tubular rivets made from the material of the softer conductor are used and subjected to salt spray and electrochemical tests. Electrical resistance measurements performed on hybrid busbars taken from the corrosion testing cabinet at the end of each exposure period allow concluding that the new injection lap riveted hybrid busbars have a better electrical performance over time due to the elimination of fasteners with a higher electrical resistivity than aluminum and copper and to the elimination of the aluminum-steel and copper-steel galvanic pairs. The capability of the injection lap riveted hybrid busbars to withstand shear forces after corrosion testing also revealed to be adequate and like those of the original (uncorroded) hybrid busbars.