Abstract
In order to study the influence of the cooling fluid parameter on the fluid flow and end part temperature in the end region of the large turbogenerator, a 330-MW water–hydrogen–hydrogen cooled turbogenerator is analyzed. The fluid velocity and pressure values from the flow network calculations are applied to the end region as boundary conditions and the losses obtained from 3-D transient electromagnetic field calculations are applied to the end parts as heat sources in the fluid and thermal coupling analysis. After solving the fluid and thermal equations of fluid–solid conjugated heat transfer, the fluid velocity and end part temperature in the turbogenerator end region are gained under the different cooling fluid parameters. The influence of different fluid velocities and fluid temperatures in the water pipe inlet, and in the fan inlet on the fluid flow and end part temperature in the turbogenerator end region is researched. The calculation results of copper shield temperature are compared with the measured values. The calculation results coincident well with the measured values. These provide the important reference for better cooling turbogenerator end region.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.