In this study, we use a apparatus that can be opened at constant speed. The voltage is set to DC 200, 300, and 500 V. The closed contact current is set to constant at 10 A at each voltage. The opening velocity is varied in the range of 1 to 200 mm/s. The contact material is Pd and Pt with low thermal conductivity. The arc duration is obtained from the voltage· current waveforms of the arc discharge, and the arc energy is obtained from the electric power waveform. In addition, arc length and contacts gap length at the time of arc extinction is obtained from the video analysis of the arc discharge light. As a result, it became clear that the arc duration and the arc energy are inversely proportional to the opening speed. These results were similar to that of Ag, W, Ni, and Cu, and the difference due to the contact material was small. The arc length immediately before the arc extinguishment became a constant value determined by the source voltage independent of the contact material and opening velocity. The value was about 30 mm at 200 V, about 60 mm at 300 V and about 110 mm at 500 V.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.