Recently, the design and construction of fiber reinforced concrete structures, such as floor slabs and precast tunnel linings, require using the actual values of the residual flexural strength instead of the average concept of the equivalent residual flexural strength ratio. An experimental study was performed to examine the direct residual flexural strengths of steel fiber reinforced concrete beams with various concrete strengths, 25, 35, and 45MPa, and fiber volume factions, 0.25, 0.375, and 0.50%. The influence of the concrete strength and fiber content in the limit of proportionality, residual flexural strength, and energy absorption capacity were evaluated. The fiber reinforced concrete beams with a strength of 45MPa showed a higher increase in the residual flexural strength immediately after concrete cracking, particularly for a fiber volume fraction of 0.5%. On the other hand, as concrete cracking propagated, the residual flexural strength and energy absorption capacity values rapidly decreased in the beams with a concrete strength of 45MPa.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.