Abstract
In recent years, for the influence of all kinds of natural disasters, the transmission tower’s collapsing or line’s damage presents a growing trend. The influence of assembly stress in transmission towers is often ignored when people analyze the accidents. To study the actual influence of assembly stress, the production process of assembly stress should be summarized and simulated. Find out the method to calculate and simulate assembly stress by using the finite element analysis software. Trussed beam hybrid finite element model is built. The ultimate load carrying capacity with the influence of assembly stress is studied. The position which is unfavorable for dimension error is determined through the variation of bar quantity and the position of dimension error. It founds that influence of assembly stress is small when there is only one pole existing size error in the transmission towers and the size error should small than 1% of the pole’s length; When there are a number of poles which are located at the tower leg existing size error will produce great influence on the Ultimate load carrying capacity of the transmission towers.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.