Abstract

The influence of ablation on the du/di behavior of an arc in a model gas circuit breaker was examined. Specifically the transition from a state without ablation in the nozzle towards states with ablation was of interest, since prior work indicated that for high currents the voltage becomes constant or du/di gets even positive if ablation is present. Measurements with different blow pressures and rectangular DC currents of varying amplitude were compared, using PMMA-nozzles and dry air as blowing gas. Ablation was measured by weighing the nozzle, scanning the cross section, and using a coordinate measuring machine. The results agreed well, and confirmed that higher pressure shifts the du/di curve towards more favorable values.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.