Abstract

This paper investigates the feasibility of using inexpensive techniques to enhance the coefficient of performance (COP) of the refrigeration cycle used in the liquefaction of natural gas. The effect of mixing the propane refrigerant with ammonia, sulfur dioxide and carbon dioxide on the performance and the work of the compressor is studied. It is shown that the mixture of ammonia-propane and sulfur dioxide-propane enhances the overall COP by 7% and 9%, respectively. The addition of ammonia and sulfur dioxide to the propane refrigerant reduces the overall compressor work by reducing the overall mass flowrate required to absorb a constant heat from the natural gas. On the other hand, the mixture of carbon dioxide-propane degrades the overall COP by 70%. The addition of carbon dioxide increases the overall mass flowrate required to absorb a constant heat from the natural gas. Interestingly, the proposed method requires small capital and running costs.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.