Abstract
Recently, as a substitute for SF <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub> gas circuit breaker, a vacuum circuit breaker with low environmental effect is attracting attention. The development of vacuum circuit breaker adapted high voltage and large current. Therefore, increase of current carrying ability is necessary for vacuum circuit breaker, and it may be possible to increase current carrying ability by the vacuum interrupters in parallel. Therefore, arc currents of vacuum interrupters in parallel are measured. In other application for nuclear experiment for large Tokomak Machine, interrupters in parallel is interrupted DC 130kA successfully and it may be also acceptable parallel operation of vacuum interrupter for the increase of interruption capacity.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.