Abstract
This paper investigates the interaction between frequency containment services (FCS) and power oscillation damping (POD) ancillary services installed in a Voltage Source Converter High Voltage DC (VSC-HVDC) line. In VSC-HVDC systems, ancillary services can be installed to maintain appropriate levels of power system stability. Both FCS and POD controllers are typically installed in the active power control loop separately. The modulation signals generated by these two ancillary services both affect the active power injected by the converter. When operating a VSC with FCS and POD ancillary services the resultant combination of the modulation signals in the active power loop may result in reduced performance. The results in this study show that performance of controllers reduces when both ancillary services are activated, particularly in low-inertia systems. Modifications to the control structures of both controllers that improve their performance under various disturbances are proposed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.