Abstract

Modern fault ride-through (FRT) standards in many countries require distributed generators to remain connected for a specified period during the fault by providing reactive current, to support voltage and prevent a massive renewable outage. As a result, short-circuit current is not constant, but it varies depending on the current and disconnection order of distributed generators (DGs). This time-varying short-circuit current complicates the estimation of the time it will take for an overcurrent relay or fuse to trip. The existing short-circuit calculation algorithms usually assume that the fault current is constant throughout the whole period of fault. This assumption may result in incorrect conclusions regarding the tripping time of protective devices in networks with high renewable penetration. This paper incorporates modern FRT standards into the fault analysis by considering the influence of fault current variations on the protective devices (relays, fuses), significantly increasing the accuracy of the estimated tripping time. Simulations carried out in a 13-bus and the IEEE 8500-node network indicate that the traditional short-circuit calculation approaches may miscalculate the tripping time of protective devices, with deviations up to 80 s, when applied to networks complying with modern FRT standards.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.