Abstract
Correct energy measurement is vital for electric energy trading. There are often stringent legal demands on the revenue metering that require periodic in situ substation verification. Traditional energy metering testing methods are not possible in IEC 61850 digital stations using a process bus. In this article, we will show that it is possible to use data analysis to verify the accuracy of energy measurement systems in substations. Our algorithms can be used as a part of the legal verification and runs remotely on-line. As a consequence, some of the periodic accuracy verification including substation visits can be abandoned. The on-line algorithms makes it possible to decrease the errors in both revenue metering systems and in other energy measurements systems in the Swedish transmission system. Measurement errors are now detected and amended much faster which reduces incorrect billing. The estimated value of incorrect billing is decreased by more than a million EUR annually. Our algorithms also provide a solution to bridge the problem to verify measurements in future fully digital substations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.