Abstract

ObjectiveTo test whether the incidence of common colds among college students in China is associated with ventilation rates and crowdedness in dormitories.MethodsIn Phase I of the study, a cross-sectional study, 3712 students living in 1569 dorm rooms in 13 buildings responded to a questionnaire about incidence and duration of common colds in the previous 12 months. In Phase II, air temperature, relative humidity and CO2 concentration were measured for 24 hours in 238 dorm rooms in 13 buildings, during both summer and winter. Out-to indoor air flow rates at night were calculated based on measured CO2 concentrations.ResultsIn Phase I, 10% of college students reported an incidence of more than 6 common colds in the previous 12 months, and 15% reported that each infection usually lasted for more than 2 weeks. Students in 6-person dorm rooms were about 2 times as likely to have an incidence of common colds ≥6 times per year and a duration ≥2 weeks, compared to students in 3-person rooms. In Phase II, 90% of the measured dorm rooms had an out-to indoor air flow rate less than the Chinese standard of 8.3 L/s per person during the heating season. There was a dose-response relationship between out-to indoor air flow rate per person in dorm rooms and the proportion of occupants with annual common cold infections ≥6 times. A mean ventilation rate of 5 L/(s•person) in dorm buildings was associated with 5% of self reported common cold ≥6 times, compared to 35% at 1 L/(s•person).ConclusionCrowded dormitories with low out-to indoor airflow rates are associated with more respiratory infections among college students.

Highlights

  • Crowded dormitories with low out-to indoor airflow rates are associated with more respiratory infections among college students

  • Other questions were about frequencies of window opening, cleaning routines and environmental tobacco smoke (ETS) exposure

  • Phase I In Phase I, 3712 students living in 1569 dorm rooms in 13 buildings answered the questionnaire, giving a response rate of 57%

Read more

Summary

Methods

In Phase I of the study, a cross-sectional study, 3712 students living in 1569 dorm rooms in 13 buildings responded to a questionnaire about incidence and duration of common colds in the previous 12 months. In Phase II, air temperature, relative humidity and CO2 concentration were measured for 24 hours in 238 dorm rooms in 13 buildings, during both summer and winter. Ethics statement Verbal consents were obtained from participants, since participants did not want to be tracked back by signature Both the study and the consent procedure were approved by the ethics committee at Tianjin University. In Phase I, demographic information, the health status of 6500 students, and building and room characteristics of 2117 dorm rooms at Tianjin University were surveyed by questionnaires. The questionnaire survey was anonymous, but building number and room number were reported by participants. Other questions were about frequencies of window opening, cleaning routines and environmental tobacco smoke (ETS) exposure

Results
Discussion
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.