Abstract

In wind turbine systems, pitch angle controllers are employed to reduce the aerodynamic power gained during high wind speeds. On the other hand, passive filters are usually used to mitigate disturbances in grid-connected voltage source converters (VSCs). To avoid the risk of instability in the grid-connected VSC, as a result of resonance in the capacitive and inductive components, it is necessary to consider damping. In this study, the low pass filter timing constant of the pitch angle controller of the doubly-fed induction generator (DFIG) wind turbine was varied considering different time constants. The best timing response of the low pass filter was further used to analyse different filter topologies, in addition to a new control strategy that uses two trap passive filters with shunt resistor–capacitor as an active damper, in augmenting the DFIG wind turbine during grid fault. Simulation studies in PSCAD/EMTDC were carried out to compare the performance of the proposed scheme with some other conventional filter solutions for the DFIG wind generator, during a severe bolted three-phase to ground fault. The simulation results demonstrate the improved performance and faster recovery of the wind generator variables after the fault considering the proposed filter scheme.