Abstract

In this study, the effect of simultaneously using two active and passive methods, namely the magnetic turbulator and the helical coil wire (HCW) turbulator, on the hydrothermal parameters of a double tube heat exchanger is being evaluated for the first time. The results are also being compared with those of a simple heat exchanger, a heat exchanger equipped with a magnetic turbulator, and a heat exchanger with a HCW turbulator insert. Finally, the most optimal option is selected using TEF. Tests have been conducted using different pitch ratios of the HCW turbulator (ranging from 2.5 to 10) and fluid flow rates (ranging from 0.5 to 4 l/min). According to the results, the usage of the HCW turbulator, magnetic turbulator, and the simultaneous use of both turbulators increases heat transfer by 237 %, 262 %, and 491 %, respectively. Additionally, the pressure drop in the presence of these two methods is 3.8 times that of a simple heat exchanger. Furthermore, with the help of TEF, the heat exchanger armed with both turbulators is chosen as the optimal option, achieving a TEF of 3.78.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.