Abstract

This paper reports the application of a static approach for assessing the steady-state loading margin to voltage collapse of the North-West Control Area (NWCA) of the Mexican Power System. The approach uses both optimal load flow (OLF) and conventional load flow (LF) solutions, and singular value decomposition of the load flow Jacobian matrix ( J). Additionally, the approach allows to determine suitable locations for corrective actions such as, the addition of new equipment or load shedding. The results shows that the combination of OLF and LF resulted in a steady-state loading margin to voltage collapse of the NWCA 7.2% higher than the case when only conventional load flow solutions were considered.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.