Abstract

This study investigated the use of an innovative Proportional Integral (PI) + dead-zone control strategy to improve pH control and to overcome the negative environmental impact associated with the currently employed on/off pH control schemes for microalgae cultivation. Scenedesmus sp. grown in anaerobically digested abattoir effluent (ADAE) was used in this study to evaluate the effectiveness of the alternative/advanced control strategy with respect to the on/off control strategy. Results obtained showed that the PI+dead-zone control strategy significantly improved the regulation of the pH level in the pond as evident by noteworthy reductions of key controller performance indicators with respect to the on/off control strategy. Additionally, the advanced control scheme was able to reduce the CO2 usage by a remarkable 59.21% (highest recorded in related literature), resulting in a reduction in CO2 associated costs (approximately 60%) and most importantly, reduction in the amount of greenhouse gas lost to the atmosphere.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.