Abstract

The paper presents an efficient and simple model-based method of on-line estimation of respiration from the current values of dissolved oxygen concentration and airflow signals. Fast estimation of respiration is important because respiration appears as the most important disturbance signal in the control of dissolved oxygen concentration, and could therefore be used for improving control efficiency. A parameter scheduling PI (proportional and integral) control scheme is proposed, where the estimated respiration signal is used for scheduling of the PI controller parameters, by using local linearization of the process dynamics. The performance of the scheduling controller is compared to a conventional PI controller in simulation using the COST simulation benchmark, and experimentally on an activated sludge process pilot plant.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.