Abstract

In the article, the distribution of symmetrical loads operating in extreme load, taking into account the total power of the consumers in the power network, was modeled by installing solar panels in apartments. As a result, as a result of the use of solar panels with a total power of 34 kW in the houses in the cable distribution network with a length of 0.444 km, a reduction of active power loss of 21382 kWh (37%) is achieved, a reduction of reactive power loss is achieved by 7309kVAR*hour (37%), the level of overloading of the cable network was 1- in the section of households, from 105% to 85%, and in the section of the last households, a decrease is achieved from 14% to 6%. In addition, it was found that the voltage drop at the ends of the apartments is not at the required level, and when the solar panels are connected, it is at the limit values.