Abstract

Protection and measurement systems in electrical substations are requested to have high availability. When considering an all-digital substation protection system, all the components and infrastructure devices (instrument transformers, processing units, merging units, intelligent electronic devices, communication network and synchronization source) contribute to the overall availability level. In particular, in this paper the availability of a distributed phasor measurement unit inspired by the standards IEC 61850, is investigated. A cost-effective solution to enhance distributed PMU reliability by means of redundancy using an IEEE 802.11 wireless network is proposed. The process bus has a wireless backup for both time synchronization protocol and sampled values packets carrying measurement information. Results are reported for a wireless network that uses software based timestamping for PTP synchronization.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.