Abstract

In order to solve the technical problems of traditional power system classic formulas that are difficult to explain the static stability limit changes of power grid interconnection lines, as well as the difficulties in improving and warning the static stability limit power of interconnection lines, this paper provides a method for improving and warning the static stability limit of power grid interconnection lines. Firstly, based on the electrical quantities measured by the wide-area measurement system (WAMS) of the power grid, the equivalent reactance of the power grid interconnection lines, and the equivalent impedance from the high voltage side and medium voltage side of the three coil transformers on both sides of the interconnection line are determined. Secondly, under pre-set operation mode and constraint conditions, the configuration quantity and capacity of the dynamic reactive power sources on the medium voltage side of the three coil transformers on both sides of the interconnection line are determined. Finally, based on the determined configuration and pre-set operation mode of the dynamic reactive power sources on the medium voltage side of the three coil transformers on both sides of the interconnection line, the historical electrical quantities measured by WAMS. The static stability limit and static stability margin of the interconnection line are calculated, and warnings are provided.