Abstract

To improve the harmonic reduction ability in input line current of 12-pulse diode bridge rectifier (DBR) using zigzag autoconnected transformer with a dc side current injection technique is presented in this paper. Conventional 12-pulse rectifier does not meet the IEEE-519 standard and therefore current injection technique at dc side is used to shape the system current waveform to minimize the harmonic distortion in the input line current. The proposed configuration uses zigzag autoconnected transformer with inherent ability of blocking zero-sequence components which eliminate the requirement of zero sequence blocking transformer (ZSBT). The current injection circuit with interphase reactor (IPR) enables to alter dc current at the rectifier output which further shapes input line currents to near sinewave. The proposed configuration is designed, simulated and analyzed in MATLAB/SIMULINK. Simulation results of proposed configuration for variation in current injection and load on input line current harmonic suppression, power quality parameters are presented in this paper.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.