Abstract

This paper suggests the possibility of improving digital power transformer protection. The establishment of inrush in power transformers is becoming unreliable in existing numerical protection. An artificial neural network (ANN) was applied to inrush detection. The saturation of protective current transformers (CT) cannot be totally eliminated despite proper dimensioning. ANN was used for the reconstruction of distorted secondary CT currents due to saturation. In both cases, an ANN was included in the protection algorithm as an extension of the existing methods, which improved the reliability of the protection operation. The paper presents the digital protection algorithm completed in this way and the laboratory equipment by means of which experimental results were obtained. The results confirm faster and more reliable recognition of transformer inrush, as well as satisfactory reconstruction of the distorted secondary CT currents.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.