Abstract
Online impulse frequency response analysis (IFRA) has proven to be a promising method to detect and diagnose the transformer winding mechanical faults when the transformer is in service. However, the existing fast Fourier transform (FFT) is actually not suitable for processing the transient signals in online IFRA. The field test result also shows that the IFRA signature obtained by FFT is easily distorted by noise. An improved method to obtain the online IFRA signature based on multi-scale complex continuous wavelet transform is proposed. The electrical model simulation and online experiment indicate the superiority of the wavelet transform compared with FFT. This paper provides guidance on the actual application of the online IFRA method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.