Abstract This paper presents distribution static compensator (DSTATCOM) with dq0 current controller and sine pulse width modulation (SPWM) switching for compensation of unbalanced nonlinear load in distribution system. DSTATCOM, connected in parallel to load at the point of common coupling (PCC), is used for supplying reactive and harmonic components of load current demand. This dq0 current controller is implemented in synchronous reference frame (SRF) rotating at fundamental frequency and consists of harmonic compensation (HC) regulator along with proportional integrator (PI) regulator. HC regulator is realized by number of sinusoidal signal integrators (SSIs) in parallel. The SSI provides high gain for tuned harmonic frequency and helps in minimizing filter current tracking error while compensating for load harmonic currents. Zero-axis controller, which compensates load neutral current and helps in obtaining balanced utility currents, is provided along with d, q controllers. SPWM switching generates inverter gating pulses at constant frequency, which reduces stress levels on VSI switches and simplifies the design of interface filter. Simulation studies of DSTATCOM load compensation with dq0 current controller are carried out in Matlab/Simulink and experimental verification is done using dSpace 1104 with Matlab real-time interface (RTI).