Abstract

This paper investigates the fault ride through (FRT) capability improvement of a doubly fed induction generator (DFIG)-based wind turbine using a dynamic voltage restorer (DVR). Series compensation of terminal voltage during fault conditions using DVR is carried out by injecting voltage at the point of common coupling to the grid voltage to maintain constant DFIG stator voltage. However, the control of the DVR is crucial in order to improve the FRT capability in the DFIG-based wind turbines. The combined feed-forward and feedback (CFFFB)-based voltage control of the DVR verifies good transient and steady-state responses. The improvement in performance of the DVR using CFFFB control compared with the conventional feed-forward control is observed in terms of voltage sag mitigation capability, active and reactive power support without tripping, dc-link voltage balancing, and fault current control. The advantage of utilizing this combined control is verified through MATLAB/Simulink-based simulation results using a 1.5-MW grid connected DFIG-based wind turbine. The results show good transient and steady-state response and good reactive power support during both balanced and unbalanced fault conditions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.