In condensers of large air-cooled chillers, VV-shaped finned-tube condenser coils are usually configured with the upper fan, often resulting in unevenly distributed flow and varying wind speed. This may causes the heat transfer rate of the condenser to fall below the intended level and negatively affects the energy efficiency of the chiller. This first part of the study attempted to investigate the effects of various configurations of condensing coils, three types of variant fin configuration (VFC) and four types of variant row configuration (VRC), on reducing the mal-distribution of airflow across compact air-cooled condensers. Using CFD airflow simulation and heat transfer analysis, the results of this study showed that VRC-designed condensers improve airflow distribution and enhance heat transfer performance. The best case (Case C4) increased the average air velocity and overall heat transfer rate of the base case (Case A) by approximately 10.3% and 5.3%, respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.