Abstract

The operation of chiller systems could take up over half of the electricity consumption of air-conditioned buildings in subtropical regions. This paper explains how to examine the effectiveness of their energy management by using data envelopment analysis (DEA). A large-scale system with seven chillers of two different capacities was studied. The scale, technical and overall efficiencies defined in DEA were calculated for each set of operating conditions comprising the system coefficient of performance (COP) and input variables: the compressor power, chiller load and temperatures at the evaporator and condenser sides. Under the existing operating strategy, the average system COP was found to be 5.73 with an average technical efficiency of 0.97. This indicates that the system operated very efficiently for most of the time. Fine-tuning the temperature-related controllable variables could achieve the highest possible COP of 5.83 with technical efficiency of one. The benefits of using technical efficiency to identify energy management opportunities are highlighted.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.