Sensitivity analysis is a conventional power grid analysis method that has been widely used in active power safety correction of power systems. This method relies on linearizing the power flow equation, assuming that the control variable change will continue to act on the power system until a new steady-state operating point is reached. However, this method ignores the quasi-steady-state physical response of power equipment to various control operations, which makes the method not suitable for real-time decision-making. Therefore, according to the improved equal and opposite quantity adjustment principle, this paper proposes a practical power flow correction control strategy, that can avoid repeated and inefficient adjustments of the system. In the proposed method, the single-machine sensitivity matrix under the AC power flow model is obtained based on the Taylor series expansion of the power flow equation. Subsequently, the multi-machine sensitivity with no dependence on the choice of the balancing machine is proposed considering the quasi-steady-state method. The study is verified on a practical system, showing that the proposed method has an error of less than 1% with a rapid computation speed. The proposed method satisfies the requirements of real-time analysis and online control strategies, which can provide a more practical approach for active power safety correction.

Highlights

  • Power system active power safety correction control is an important part of safety control and a means of ensuring safe and high-quality operation of power systems [1]

  • This paper proposes an improved correction strategy for power flow control based on multi-machine sensitivity analysis

  • The multimachine sensitivity matrix was obtained by the quasi-steadystate method

Read more

Summary

INTRODUCTION

Power system active power safety correction control is an important part of safety control and a means of ensuring safe and high-quality operation of power systems [1]. For real-time alleviation of equipment overload and the increase of the system static load ability, the sensitivity of vulnerability index of generation units was proposed in [42] It was accurately computed by an actual AC power flow incorporating the automatic generation control model. On the basis of previous research, this paper presents an innovative multi-machine sensitivity analysis method, which considers the quasi-steady-state physical response of power equipment to various control operations. It is more suitable for real-time analysis and horizontal comparison, despite the selection of a balancing machine.

MULTI-MACHINE SENSITIVITY METHOD CONSIDERING THE QUASI-STEADY-STATE RESPONSE
IMPROVED EQUAL AND OPPOSITE QUANTITY
Findings
CONCLUSION