Abstract

The AC-filter configuration, reactive power consumption, reactive power control function, switching and replacement strategy in SHANSHAN UHVDC converter station are introduced in detail. The various types of AC filters in the converter station are evenly configured in the large groups of filters based on their quantity. And the related types of filters within a large group are usually switched preferentially. The problem of this switching strategy that may cause large impact on the AC system and long reactive power recovery time during the large group of AC filter bus lines fault are analyzed. Then an improved strategy that the needed filters with same type are equally switched on the large AC-filter group is proposed. The proposed strategy can effectively reduce the influences of AC-filter bus fault to the AC system which will give some references for the design and operation of subsequent UHVDC projects.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.