Abstract
The behavior of transients in water pipe networks is well understood but the influence of modulating control valves on this behavior is less well known. Experimental work on networks supplied through pressure reducing valves (PRVs) has demonstrated that, in certain conditions, undesirable phenomena such as sustained or slowly decaying oscillation and large pressure overshoot can occur. This paper presents results from modeling studies to investigate interaction between PRVs and water network transients. Transient pipe network models incorporating random demand are combined with a behavioral PRV model to demonstrate how the response of the system to changes in demand can produce large or persistent pressure variations, similar to those seen in practical experiments. A proportional-integral-derivative (PID) control mechanism, to replace the existing PRV hydraulic controller, is proposed and this alternative controller is shown to significantly improve the network response. PID controllers are commonly used in industrial settings and the methods described are easy to implement in practice.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.