This paper proposes a method for characterizing voltage dips based on the space phasor model of the three phase-to-neutral voltages, instead of the individual voltages. This has several advantages. Using a K-means clustering algorithm, a multi-stage dip is separated into its individual event segments directly instead of first detecting the transition segments. The logistic regression algorithm fits the best single-segment characteristics to every individual segment, instead of extreme values being used for this, as in earlier methods. The method is validated by applying it to synthetic and measured dips. It can be generalized for application to both single- and multi-stage dips.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.