Abstract

This paper deals with a modeling of components and calculation of transient overvoltages that build up on the transformer primary terminals after the transformer has been switched off by a vacuum circuit breaker (VCB). The transformer is connected to the circuit breaker by a cable. The transient overvoltages are calculated for different cable lengths, and the cumulative probability of different arc angles is investigated. In this study two cases are considered: transient overvoltages due to steady-state magnetizing current switching, and transient overvoltages due to inrush current switching. It is shown that the case of inrush current switching is worse, as virtual current chopping is possible. The cable is modeled by pi sections, whereas the transformer model is based on a terminal impedance. The VCB re-ignitions are modeled by means of withstand voltage characteristics and high-frequency quenching capability. Due to shortage of field tests, this work uses only literature references to compare the results with actual measurements.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.