Abstract
Very fast transient overvoltages (VFTOs) due to switching operations can appear between the gas-insulated substation (GIS) enclosures and the cable sheaths and between these grounding parts and the substation Earth structures. These VFTOs achieve hundreds of kilovolts, provoking hazardous disruptive discharges for human safety. This paper includes a sensitivity analysis of the different parameters in order to establish criteria to be adopted in the grounding system design of the GIS structures and the cable connection to mitigate transient overvoltages. The use of bypass surge voltage limiters (SVLs) between the GIS enclosure and the cable sheath is also needed to avoid uncontrolled discharges. The selection of these SVL according to insulation coordination rules is presented in this paper, ensuring electrical safety without affecting the current mode of exploitation of the 220-kV GIS or the cable.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.