Abstract
The active frequency drift (AFD) method is an effective method to detect islanding in grid-connected photovoltaic systems. However, it has some inherent drawbacks, such as generating higher harmonics. In order to reduce the harmonics and non-detection zone (NDZ), various improved AFD methods have been proposed, but they still suffer from high harmonics and reduced detection speed. To overcome these limitations, this paper proposes an innovative islanding detection technique based on AFD. Analysis reveals that the proposed method reduces harmonics by 68% compared to conventional AFD and has a larger chopping factor. Therefore, this technique offers several distinct advantages, including accelerated detection speed, reduced NDZ and harm caused by disturbances, and improved power quality. Furthermore, to verify the harmonic impact of this proposed islanding detection method, simulations and analyses are conducted using simulation software of Matlab/Simulink. An experimental prototype is set up in Laboratory. The simulation and experimental results demonstrate the superiority of the proposed method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.