Abstract
In this work, a novel technique based on second order sequence filter and proportional resonant controller is proposed for control of universal active power filter integrated with PV array system (UAPF-PV). Using a second order sequence filter and sampling it at zero crossing of instant of the load voltage, the active component of distorted load current is estimated which is further used to generate reference signal for shunt active filter. The proposed method has good accuracy in extracting fundamental active component of distorted and unbalanced load currents with reduced mathematical computations. Along with power quality improvement, the system also generates clean energy through the PV array system integrated to its DC-bus. The UAPF-PV system integrates benefits of power quality improvement and distributed generation. The system performance is experimentally evaluated on an experimental prototype in the laboratory under a variety of disturbance conditions such as PCC voltage fall/rise, load unbalancing and variation in solar irradiation.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.