Abstract

In this study, the numerical analysis of the radiant floor system was investigated for a building in the presence of PCM inside the external walls as well as the roof at a thickness of 2 cm. By injecting cold/warm fluid into the radiant tubes inside the roof, the cooling/heating requirements were met. Several PCMs with identical thermal properties (except melting point) were selected and based on numerical analysis, the energy utilization in the heating/cooling sections was evaluated by comparison with the simple building (without PCM). Four main variables were defined for the neural network, and energy consumption was trended for two climate zones, Shenyang (41.7922°N, 123.4328°E), and Zhengzhou (34.7578°N, 113.6486° E). For each region, the PCM with the best phase transition was selected and it was realized that for the first region, energy consumption was diminished by 12.6% and for the second region by 15.9%. According to the temperature conditions and radiation intensity in the environment, the ANN could forecast annual energy utilization with an error of less than 6%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.