Abstract

To eliminate uncertainties arising from assumed constants involved in the calculation of sequence impedances, hield measurements of 60 cycle positive and zero sequence impedances of 2 sizes of 3-conductor underground power cable were made on the 27 kv system of a large eastern metropolitan company; the results are reported in this paper. While the principal results are applicable only to the particular system involved, they show that without the support of the experimental data the calculation of zero sequence impedance of feeder circuits in a system of this kind can be at best only roughly approximate.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.