Abstract
This paper presents a new impedance based fault location method in the case of phase to phase and three phase faults. This method utilized the measured impedance by distance relay and super imposed current factor, which is the ratio of post-fault current to super imposed current, to discriminate the fault position on the line. This method is robust against the fault resistance. The presented method only uses the measured impedance by distance relay, the super imposed current factor and few data which could be achieved through the SCADA based databases. (5 pages)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.