Abstract

Islanding detection is critical to the safety of grid-tied inverters. This paper presents an impedance-based analysis of the active frequency drift (AFD) islanding detection method. To study this method, the output impedance of a grid-tied inverter is modeled. The $Z_{qq}$ of the inverter impedance features a negative incremental resistor, whose magnitude is equal to the dc impedance magnitude of the local load defined by the test standard. With a large value of feedforward gain $N$ in the AFD method, the phase of $Z_{qq}$ is shown to drop below 180°. Under an islanding condition, due to a lack of phase margin, the inverter system becomes unstable with a frequency drift away from its steady state. The islanding condition is then identified by a frequency detection unit. Experimental results verify the analysis.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.