Abstract

In order to accomplish specific compensation objectives a static synchronous series compensator (SSSC) may be controlled by several ways. The most common control modes of the SSSC are: (1) constant voltage mode, (2) constant impedance emulation mode, and (3) constant power control mode. Moreover, to improve the dynamic performance of the system, a SSSC may be equipped with supplementary controllers, such as damping controls. Therefore, this paper investigates the impacts of different SSSC control modes on small-signal and transient stability of a power system. The performance of different input signals to the power oscillation damping (POD) controller is also assessed. The stability analysis and the design of the SSSC controllers are based on modal analysis, non-linear simulations, pole placement technique, and time and frequency response techniques. The results obtained allow to conclude that the usage of the SSSC in the constant impedance emulation mode is the most beneficial strategy to improve both the small-signal and transient stability.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.