Abstract

Curtailment losses for large-scale hybrid wind–solar photovoltaic (PV) plants with a single grid connection point are often calculated in 1 h time resolution, underestimating the actual curtailment losses due to the flattening of power peaks occurring in shorter time frames. This paper analyses the curtailment losses in hybrid wind–PV plants by utilising different time resolutions of wind and PV production while varying the grid cut-off power, wind/solar PV farm sizes, and shares of wind/PV capacity. Highly resolved 1 s measurements from the operational wind farm and pyranometer are used as an input to specialized wind and PV farm power production models that consider the smoothing effect. The results show that 15 min resolution is preferred over 1 h resolution for large-scale hybrid wind–PV plants if more accurate assessment of curtailment losses is required. Although 1 min resolution additionally increases the estimation accuracy over 15 min resolution, the improvement is not significant for wind and PV plants with capacity above approx. 10 MW/10 MWp. The resolutions shorter than 1 min do not additionally increase the estimation accuracy for large-scale wind and PV plants. More attention is required when estimating curtailment losses in wind/PV plants with capacity below approx. 10 MW/10 MWp, where higher underestimation can be expected if lower time resolutions are used.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.