Abstract

The shunt reactor will affect the sub synchronous oscillation characteristics of the wind power system, and there is no paper that analyse this aspect. To this end, in the DFIG via series compensation transmission power system, use impedance scanning method to measure the total equivalent impedance of system side and DFIG side, the mechanism of the influence of the installation position and capacity of the shunt reactor on the sub synchronous oscillation characteristic of the system is analysed. The analysis results show that the larger capacity of shunt reactor, equivalent impedance effect is larger, the installation position that is very near the fan can reduce the resonant frequency and increase the resistance of resonance point, being far from the fan will increase the resonant frequency and the absolute value of the negative resistance in the resonance points, besides, the effect of parallel capacitor on system impedance is very small. Finally, the correctness of the theoretical analysis is verified by the time-domain simulation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.