Abstract
The Under-Frequency Load Shedding (UFLS) scheme is an emergency measure in place to prevent system collapse in the event of a large generation deficit relative to demand at any moment in time. However, the effectiveness of traditional UFLS schemes may be compromised as network power flows change due to the growth of distributed generation (DG) and a reduction in system inertia. This study has shown some of the issues affecting the UFLS protection system with rising installed capacities of DG in the Great Britain power system. Simulation results show how the effectiveness of the scheme is challenged with current and future expected DG installed capacities and the risk of over shedding demand due to the scheme’s current settings is evaluated. Many proposed improvements to traditional load shedding schemes are based on upgrades to network monitoring and communication systems, which are not yet fully available. This study evaluates more readily available solutions, including relocation of under-frequency relays and reducing the time delay of the scheme, which may provide interim improvements to the UFLS scheme, based on a case study in GB.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.