Abstract

The authors developed an equivalent circuit for the synchronous generator and a transformer unit. It could help determine the magnetizing current parameters for a generator transformer when the magnetic system is saturated due to geoinduced currents provided the synchronous generator has an automated excitation controller. The authors identified the dependencies of the magnetizing current fundamental harmonic on the magnetizing power of the generator transformer and the geoinduced current value. The article provided numerical values for the fundamental harmonic of the magnetizing current and power at various geoinduced current values for a TDTs 400000/242/20 generator transformer. It is demonstrated that the increase in the reactive power of the synchronous generator results from the operation of the automated excitation controller aimed at maintaining the constant voltage in the generator buses by the excitation current increase. The authors identified the safe value ranges for the excitation order to compensate the increase in the magnetizing power of the generator transformer without any current overloads on the rotor and stator or any reduction in the synchronous generator active load.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.