The use of non-linear devices causes unfavourable changes in the operation of the power system. First of all, they are a source of higher harmonics in network waveforms, which tend to increase the eddy currents. Their effect consists in raising the temperature of transformer cores. This, in turn, translates into their failure rate and fire safety, including reducing the actual value of rated power. The article describes the results of experimental studies carried out on a large scale. An analysis was performed of the quality of electric power depending on the type of network load. The results have shown that the increase in the use of non-linear receivers such as LED lighting, electronic chargers, inverters, etc. may have a tangible impact on the fire hazard of distribution transformers. Examples of calculations have been presented, which prove the necessity of taking into account the influence of higher harmonics on the reduction of the real rated power of power transformers.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.